Quick answer

ASTM E1155 is a test method for random traffic concrete floors. Heights are measured along straight lines across the slab and turned into two scores:

  • FF (floor flatness): how bumpy the surface is over short distances.
  • FL (floor levelness): how far the surface departs from its design level over longer distances.

The higher the number, the better the floor. A specification reads something like FF 35 / FL 25, flatness first.

We carry out floor flatness surveys with 3D laser scanning, tied to control set out by total station, so the whole floor is recorded and not only the lines that are tested.

Which edition: E1155M-96 or E1155/E1155M-23?

Specifications often quote “ASTM E1155M-96”. That is the metric edition approved in 1996 and reapproved in 2001 and 2008. It was revised in 2014 and withdrawn in 2023, when ASTM merged the metric and imperial versions into a single document, ASTM E1155/E1155M-23.

In practice:

  • If your specification names E1155M-96, the survey is still possible. Confirm with the specifier whether they want the 1996 edition followed or the current one.
  • The 2014 revision is the one that first allowed a laser imaging device (a laser scanner) to collect the readings.
  • The F-numbers themselves, and what they mean, are the same across editions.

What FF and FL numbers mean

Both figures are calculated from height readings taken at regular steps along sample lines.

FF compares readings 300 mm apart (one foot in the imperial version). It describes the short bumps and dips that a forklift, a pallet truck or a racking baseplate feels.

FL compares heights 3 m apart (10 ft). It describes the overall tilt or roll of the slab away from its design level.

The scale is linear. A floor at FF 40 is twice as flat as one at FF 20.

Typical values used in specifications:

Floor class FF (flatness) FL (levelness)
Conventional 20 15
Moderately flat 25 20
Flat 35 25
Very flat 45 35
Super flat 60 40

These classes come from American Concrete Institute guidance (ACI 117 and ACI 302.1R), which is where most FF and FL specifications originate.

Overall and local values

A specification normally sets two figures for each number:

  • The specified overall value, which the floor as a whole must reach.
  • The minimum local value, which every individual section must reach. Under ACI 117 this is 60% of the overall value unless the specification says otherwise.

A floor can pass overall and still fail in one bay, so the report gives results section by section.

Where the test applies

  • Random traffic floors only. E1155 is for floors where vehicles and people can travel in any direction. Very narrow aisle warehouses, where trucks follow fixed wheel tracks, are defined traffic floors and are measured with a different method.
  • New slabs are tested early. The standard expects readings within 72 hours of the slab being finished, before curling and joint shrinkage change the surface.
  • Suspended slabs. Elevated slabs deflect under their own weight, so they are normally given an FF figure only.

How we survey a floor

  1. Control by total station. We set out survey control around the floor with a robotic total station, so every scan sits on one accurate level datum and grid.
  2. 3D laser scanning. The floor is scanned with a FARO laser scanner from a network of positions. This records the whole surface as a point cloud, not only a set of lines.
  3. Profiles and analysis. Sample lines are taken from the point cloud and run through software we wrote in-house, which uses the height readings along each line to calculate the FF and FL numbers for each section and for the floor as a whole.
  4. Report and drawings. You receive the results with a plan showing where each line and section sits.

Because the whole floor is scanned, the same data can produce a coloured level plan showing every high and low spot, which is often more useful for planning remedial work than the F-numbers alone.

Scanning has limits and it is better to know them up front. Every scanner has measurement noise, and its effect on the result grows as the specified F-numbers rise. For most warehouse and commercial floors this is not a problem. For very flat and super flat specifications, tell us the figures before we quote so we can confirm the method suits them.

Surveying a floor that is years old

Most of the warehouse floors we have surveyed had been in use for years. That is a different job from testing a new pour, and the report should be read differently:

  • The survey shows the floor as it is now, including curling at joints, settlement and wear.
  • It cannot prove whether the original contractor met the specification, because that test belongs in the first 72 hours.
  • It is useful when a building is changing use: new racking, taller or faster trucks, automated vehicles, a new floor finish, or a tenant who needs the floor to meet a stated standard.
  • It shows where grinding, filling or a new topping is needed, and gives a baseline to check the repair against.

ASTM E1155, TR34 and BS 8204 compared

A UK floor flatness specification will name one of three methods. They are not interchangeable and there is no exact conversion between them.

ASTM E1155 BS 8204
Where it comes from United States United Kingdom
Typical use Floors built to American or international specifications Screeds and floors receiving a floor finish
How the floor is judged FF and FL numbers calculated from readings along sample lines Largest gap under a 2 m straightedge
Result A statistical score for each section and the whole floor Pass or fail at each place tested

BS 8204 is the simplest. A 2 m straightedge is laid on the floor and the largest gap beneath it is measured. There are three classes: SR1 allows 3 mm, SR2 allows 5 mm and SR3 allows 10 mm.

TR34 is the Concrete Society’s guide to industrial ground floors and is the usual reference for UK warehouses. It separates free movement areas, where vehicles travel anywhere, from defined movement areas such as very narrow aisles, and sets separate classes and limits for each.

ASTM E1155 tends to appear in the UK where the client, tenant or design team works to American standards, for example on distribution centres, data centres and retail fit-outs for international operators.

If your specification does not say which method applies, ask the specifier before the survey. We can survey to any of the three.

What to send us for a quote

  • The site address and the approximate floor area.
  • The specification: the standard named, the FF and FL (or other) figures required, and any minimum local values.
  • Whether the slab is new or existing, and for a new slab, the pour dates.
  • Access details: working hours, whether the floor will be clear of stock and racking, and any site rules.

Prices depend on the area, the location and the complexity of the building. Send us the details and we reply with a fixed price within one working day.

Frequently asked questions

What is ASTM E1155M-96?

It is the 1996 metric edition of the ASTM test method for FF floor flatness and FL floor levelness numbers. It has since been replaced. The metric and imperial versions were merged into one standard, ASTM E1155/E1155M, in 2023. Many specifications still quote the 1996 reference, and the F-numbers it produces mean the same thing.

What is a good FF and FL number?

It depends on what the floor is for. As a guide, FF 20 / FL 15 is a conventional floor, FF 25 / FL 20 is moderately flat, FF 35 / FL 25 is flat and FF 45 / FL 35 is very flat. The figures that matter are the ones in your specification.

Can a laser scanner be used for an ASTM E1155 survey?

Yes. The standard has allowed a laser imaging device since its 2014 revision. Scanner noise matters more as the specified F-numbers rise, so tell us the figures you are working to when you ask for a quote.

Can you test a floor that has been in use for years?

Yes, and most of the warehouse floors we have surveyed were several years old. The result is a record of the floor as it is today. It cannot show whether the slab met its specification when it was laid, because the standard expects that test to be done within 72 hours of finishing.

Is ASTM E1155 the same as TR34?

No. TR34 is the Concrete Society guide normally used for UK industrial floors and it has its own classes and limits. There is no exact conversion between F-numbers and TR34 classes, so the floor should be surveyed to whichever method your specification names.

How much does a floor flatness survey cost?

It depends on the floor area, the location and how complicated the building is, so every survey is quoted individually. Send the address, the approximate area and the specification and we reply within one working day.